Off-grid inverter: What size do you need?

Updated

An off-grid inverter turns the direct current (DC) stored in your battery bank into the alternating current (AC) that household outlets and appliances use. To size one, its continuous rating has to cover everything you’ll run at the same time, plus a margin of about 25%. Its surge rating has to cover the brief jolt of power that motors draw when they start. Then match its input voltage to your battery bank and choose a pure sine wave model.

This guide explains how to add up your loads, gives a worked example, and covers sine wave types, battery voltage, the difference between plain inverters, inverter-chargers and all-in-one units, how much power an inverter draws while idle, and safe installation. It covers battery-based off-grid inverters only. Grid-tied string inverters and microinverters, which feed power straight into the grid without batteries, are a different product.

What size inverter do you need

Every inverter has two power ratings, and you need to check both:

Find the running watts on each device’s label or datasheet, or measure them with a plug-in watt meter. Starting watts are harder to find: some manuals list them, and a clamp meter with an inrush setting can measure them. Without a figure, allow about three times the running watts for motor loads, and more for well pumps.

List your loads in a table with both columns:

Device Running watts Starting watts
Fridge 120 600
Water pump 250 750
Laptop 60 60
LED lights 40 40
Microwave 1,000 1,000

These figures are hypothetical, so use your own devices’ ratings. Devices without motors start at about their running watts.

Worked example

Using the load table above, here’s how to size an inverter for a cabin:

Continuous rating: if everything ran at once, the running watts would total 120 + 250 + 60 + 40 + 1,000 = 1,470 W. Add 25%: 1,470 × 1.25 ≈ 1,840 W. A 2,000 W inverter covers it.

Surge rating: the worst case is the fridge and the pump starting at the same moment while everything else runs. That’s 600 + 750 + 60 + 40 + 1,000 = 2,450 W for a few seconds. Many 2,000 W inverters are rated to surge to about twice their continuous rating, but check the datasheet. The figure varies between models, and so does how long the inverter can hold it.

What made the difference: without the microwave, the same cabin would need only about 600 W continuous, and a 1,000 W inverter would do. One large appliance often decides the inverter size, so it’s worth asking whether you need it on the inverter at all. A propane stove or a generator for occasional heavy use can let you choose a much smaller inverter.

Pure sine wave vs modified sine wave

Inverters produce one of two kinds of AC:

Devices that need pure sine wave, or run poorly without it, include:

Modified sine wave inverters cost less, but a typical off-grid system runs at least one of these devices. Choose pure sine wave unless the inverter will only ever power simple resistive loads.

Match the inverter to your battery voltage

An off-grid inverter’s DC input voltage must match your battery bank: 12 V, 24 V or 48 V. The current it draws from the batteries is roughly its output watts divided by the battery voltage, plus about 10% more for its own losses:

Inverter load At 12 V At 24 V At 48 V
1,000 W About 90 A About 45 A About 25 A
2,000 W About 185 A About 90 A About 45 A
3,000 W About 275 A About 140 A About 70 A

High currents need very thick, expensive cable and large fuses, and they waste more energy as heat. That’s why larger inverters belong on 24 V or 48 V banks. A rough guide: 12 V for inverters up to about 1,000 W, 24 V up to about 3,000 W, and 48 V above that.

Your batteries also have to deliver that current. Lithium batteries with a built-in battery management system (BMS) have a maximum continuous discharge current, so a big inverter may need several batteries in parallel even if you don’t need their extra capacity. Our guide to building a solar battery bank covers choosing a system voltage and wiring the bank.

Inverter, inverter-charger or all-in-one

Off-grid inverters come in three common forms:

Idle draw and efficiency

An inverter uses power just by being switched on, even with nothing plugged in. This idle draw, often listed as “no-load current” or “no-load power”, can be a few watts for a small inverter and tens of watts for a large one. That adds up over a day: a hypothetical 30 W idle draw left on for 24 hours uses 720 Wh. That’s a large share of a small cabin’s daily budget.

To keep idle losses down:

Inverters are also less efficient at very light loads. Most run at about 90% efficiency or better near their rated load, but much lower when lightly loaded, which is another reason to size close to your real needs.

Safety and installation

An off-grid inverter draws high currents from the battery bank, so the DC side needs the most care:

For where the inverter fits in a complete system, see our guide to planning and building a DIY solar system. Once the inverter and batteries are chosen, the next step is wiring the panels: our guide to connecting solar panels in series or parallel shows each layout.

Frequently asked questions

Can I run a fridge on a 1,000 W inverter?

Usually, yes. Most efficient household fridges run on a few hundred watts or less, and a pure sine wave 1,000 W inverter with a good surge rating can usually start one. Check the fridge’s running and starting watts against the inverter’s continuous and surge ratings, and leave room for anything else running at the same time.

How many batteries do I need for a 3,000 W inverter?

That depends on how long you’ll run it and on your battery voltage. For run time, multiply the load by the hours you need, then size the bank with the formula in our battery guide. For current, a 3,000 W load draws about 140 A at 24 V, so the bank must be able to supply that continuously. With lithium batteries, that may mean two or more in parallel, depending on each battery’s discharge rating.

Is a bigger inverter better?

Not past what you need. A bigger inverter costs more, draws more power while idle and runs less efficiently at light loads. Size it to your largest realistic combined load plus a margin, and make sure the surge rating covers your motor starts.

Can I use a grid-tied inverter off grid?

No. A grid-tied inverter needs the grid to operate and shuts down when the grid is down, and most can’t run from a battery bank. Off-grid and hybrid systems need an inverter designed to run from batteries.